132 Configuring the ViconNet System XX112-36-00 Rev 909 Kollector Hybrid Network Digital Video Recorder
Activating Relays in Macros
The Kollector Force rear panel has sixteen relay outputs that can be toggled between the states Open (Off)
and Cl
osed (On), or Momentarily enabled for a set duration. On system start up, the relay state is Normally
Opened (NO).
These relays can be used to drive indicators and alarm enunciators and to enable or disable devices. Within
a macro, any number of relays can be activated between as many states as desired. The relay can be
directly connected to a switching load with maximum ratings of 60 VAC or DC at 1.0 Amp current.
To activate a relay in a macro:
1. Follow steps 1 to 6 of the To create a macro procedure.
OR
Select a macro from the list at the top of the Macro Editor window and click Edit Macro.
2. To configure a relay function in the macro, click the Relay button. The relay configuration options are
displayed at the bottom of the window.
3. Select On (Closed), Off (Open) or Momentarily (configurable between 500 and 2500ms).
4. Click Apply.